cRIO and WAGO over EtherCAT: channels in a file, not in the code

Lessons learned from a cRIO EtherCAT master driving WAGO I/O under LabVIEW RT, and from the rule that simplifies everything: channels in a file.

On several test benches, I have used a CompactRIO (cRIO) controller as an EtherCAT master to drive remote WAGO inputs and outputs, with a LabVIEW Real-Time application. The topic: the architecture I chose, what you need to know about EtherCAT on the NI side, and the design rule that has made the biggest difference to these projects.

Why this architecture

  • The cRIO runs the real-time application and acts as the EtherCAT master. Its second Ethernet port, switched to EtherCAT mode, is reserved for the field network; the first remains dedicated to the development PC.
  • WAGO 750-354 couplers host the I/O modules on the rail and expose them over EtherCAT. They are daisy-chained port to port, without a switch: the frame turns round at the last coupler and returns to the master.
  • The WAGO 750/753 system offers a very wide choice of modules (digital, analogue, special) at a moderate cost, as close as possible to the wiring.
Topology: the development PC, the cRIO master and the WAGO nodes chained on a single EtherCAT line (figure in French)
Topology: the development PC, the cRIO master and the WAGO nodes chained on a single EtherCAT line (figure in French)

EtherCAT on the NI side: the Scan Engine is in charge

  • One frame per cycle: each slave reads and writes its share of the frame on the fly. A counter (Working Counter) reports within the same cycle that a slave has not processed its data.
  • The NI Scan Engine publishes each data point as an I/O variable and refreshes all channels together, at a single period. It does not buffer: a value not read before the next scan is lost.
  • The Scan Engine mode sets the slave states: in Active mode they go to Operational; in Configuration mode they return to Pre-Operational. Any deployment that changes the project forces Configuration mode.
  • A third-party slave such as the 750-354 only appears in the project after its description file (ESI) has been imported and LabVIEW restarted. Otherwise it remains an "Unknown Device".
The Scan Engine mode drives the state of the EtherCAT slaves (figure in French)
The Scan Engine mode drives the state of the EtherCAT slaves (figure in French)

The core rule: no hard-coded channels

Dragging I/O variables onto the block diagram is fine for a prototype. On a bench that evolves, the name of every channel ends up frozen in the code. So I separated two levels of configuration:

  • The network configuration, managed by NI: the imported ESI file, then the topology (master, couplers, modules, scan period) saved in the LabVIEW project and deployed to the cRIO.
  • The channel configuration, managed by the application: a file that maps each I/O variable to a functional alias, a type, a direction, scaling and a fallback value.
Two configurations meet at the cRIO I/O variables (figure in French)
Two configurations meet at the cRIO I/O variables (figure in French)
  • A channel manager reads the file at start-up and refuses to start the control loop if a channel does not exist, a type does not match or an alias is duplicated.
  • The application only knows the aliases, never the hardware paths.
  • Reading a whole module costs far less than reading channel by channel: the manager reads by module, then distributes the values by alias.

The result: a change of wiring or sensor is handled without recompiling, and the same application serves several benches that differ only in their channel file.

Points to watch

  • The order of the modules in the project must match the physical order on the rail: it sets the coupler's process image. Any mismatch shifts all the channels.
  • The versions of the EtherCAT driver and LabVIEW must be compatible: I freeze them for each project and record them.
  • The safe state: on loss of communication, the WAGO coupler forces all its outputs to 0. I therefore wire each output so that 0 is the safe state, and I include a cable disconnection test in acceptance.
  • Recovery: after a disconnection, the coupler waits for an acknowledgement from the master. My application monitors the state of each slave and provides the recovery sequence.
  • Powering a node: a power supply module after the coupler, an end module at the end of the rail, and a power budget checked with WAGO Smart Designer before ordering.
  • In operation, the application starts as an executable on the cRIO, never from the development environment: running a VI triggers a deployment and can change the Scan Engine mode.

Key takeaways

  • Most difficulties come from configuration (ESI import, module order, versions), not from the EtherCAT protocol itself.
  • Declaring channels in a file rather than in the code makes the bench modifiable without recompiling.
  • Safety is designed into the wiring: 0 must be the safe state of every output, and disconnection is tested during acceptance.

Further reading

NI, NI-Industrial Communications for EtherCAT and the NI Scan Engine, ni.com; NI, EtherCAT on CompactRIO, ni.com; WAGO, 750-354 Fieldbus Coupler EtherCAT, wago.com

Did you find this article useful?

Rate it from 1 to 5 stars. Anonymous, no sign-up.

Thank you! Your rating: 1 out of 5. You can change it by clicking another star.

Thank you! Your rating: 2 out of 5. You can change it by clicking another star.

Thank you! Your rating: 3 out of 5. You can change it by clicking another star.

Thank you! Your rating: 4 out of 5. You can change it by clicking another star.

Thank you! Your rating: 5 out of 5. You can change it by clicking another star.

Too many ratings sent in a short time. Please try again in an hour.

Your rating could not be saved. Please try again later.

@NathanLefeuvre

Comments

    Leave a comment

    Every comment is reviewed before it is published.